664
3) Ferrite core and cable clamp types
Cable clamp
Type: AD75CK (Mitsubishi)
Ferrite core
Type: ZCAT3035-1330 (TDK ferrite core)
4) Cable clamp mounting position
Refer to Page 656, Appendix 8.1.3 (2).
(c) I/O signal lines
Ground the shield section of an I/O signal cable (including common line) in the same way as explained in Page
655, Appendix 8.1.3 (1) when it is extended out of the control panel.
(d) Extension cable
Ground the shield section of an extension cable in the same way as explained in Page 655, Appendix 8.1.3 (1)
when it is extended out of the control panel.
(2) Power supply module
The following table lists the precautions required for each power supply module. Always observe the items noted
as precautions.
*1 Installing a filter to a power line is not required if the version of the A1S63P is F or later.
Make sure to use the CE-marked 24VDC panel power equipment.
Cable length Prepared part
Number of ferrite cores
1 axis 2 axes 3 axes
Within 2m AD75CK 1 1 1
2m to 10m
AD75CK 1 1 1
ZCAT3035-1330 1 2 3
Model Precautions
A1S61P, A1S62P, A61P, A62P Not usable
A1S63P
*1
, A163P
Use the CE marked 24VDC panel power equipment.
A1S61PEU, A1S62PEU, A1S61PN, A1S62PN,
A61PN, A61PEU, A62PEU, A68P
Always ground the LG and FG terminals after short-circuiting them.