MITSUBISHI ELECTRIC 7011A SERIES UPS
MITSUBISHI
ELECTRIC
7011A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-2
This UPS does not include an AC input circuit breaker (MCCB) to protect the bypass and
main input circuit. The AC input circuit breaker (MCCB) is to be field supplied and
installed. Circuit breaker (MCCB) specifications are as follows:
Capacity
(kVA)
AC input
Voltage (Vac)
AC input Rating
(Aac)
Recommended
Breaker (A)
6 208 26.4 35
8 208 35.2 45
10 208 44.0 60
12 208 52.8 70
AC output and DC input overcurrent protection and disconnection devices shall be field
supplied and installed.
WARNING 2