MITSUBISHI ELECTRIC 7011A SERIES UPS
MITSUBISHI
ELECTRIC
7011A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
2-5
B) Normal Mode
FIGURE 2.4 Tree Diagram of LCD Display (Normal Mode)
BATTERY 216V
CHARGE
Measure
OUT1 120V 60.0Hz
OUT2 120V 60.0Hz
OUT1 100A 100%
12.0kW 100%
OUT2 100A 100%
12.0kW 100%
INPUT 240V
60.0Hz
M enu
Top P a ge
CLEAR key
MEASURE
¥
LOG
¥
SILENCE
¥
SETUP
M
anual(UP/DOWN Key)
or Auto Scroll
O utput Voltage
OUT VOLTAGE ADJ
0.0 -> +2.0%
B attery Check
BATTERY CHECK
- CHECKING -
Time
MONTH/DATE /‘YEAR
10 / 14 / ‘00
HOUR : MINUTE
17 : 28
Scroll Speed
SCROLL SPEED
1 -> 0 SEC
Bypass O peration
LOAD ON BYPASS?
ON
¥
SCROLL
¥
BYPASS_OP
Setup
BATT_CHK
¥
TIME
¥
VOLT_ADJ
¥
NEXT>
R
eturn here with Clear Key
Log
( 10 items / 10 pages )
( 1) 22:05 10/14
+271
INV1 O.C.
( 2) 22:04 10/14
+806 OVERLOAD
Next page
Measure OUT1:
OUT2:
L1-N
L2-N
Log +[code]:
- [code]:
Occurred
Cleared
Set up BATT_CHK
TIME
VOLT_ADJ:
SCROLL:
BYPASS_OP:
Start the self battery test operation.
Set the day and time.
Adjust the output voltage.
Set the log page scroll speed.
Select the output source.