EasyManuals Logo

Mitsubishi 7011A SERIES User Manual

Mitsubishi 7011A SERIES
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
MITSUBISHI ELECTRIC 7011A SERIES UPS
MITSUBISHI
ELECTRIC
7011A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-8
The rotary maintenance bypass switch is shown as 52CS in Figure 1.4. 52CS is a two position
four point make-before-break transfer switch.
The two positions are identified as NORMAL and BYPASS. In the NORMAL position the load is fed
by the UPS - either through the inverter or through the static bypass line. In the BYPASS position
the load is powered by an external source such as the utility or a generator. This transfer operation
must be made while the UPS is in the static bypass mode.
For transfer procedure to place the UPS in maintenance bypass mode, or from bypass mode to
normal operation mode, refer to section 3.6 Maintenance Bypass Set-up Procedures.
(For Service Personnel Only)
FIGURE 1.5 UPS Parts Location(6kVA)
.
1.Relay I/F PCB
RYER-A
UPS module
FRONT VIEW
Converter &
Inverte
r
Battery
Display PCB
DPAU-63
I/O Module
3.Module Connection
terminal
Cooling fan
2.Maintenance bypass
transfer switch
52CS
Main PCB
UPFR-L

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi 7011A SERIES and is the answer not in the manual?

Mitsubishi 7011A SERIES Specifications

General IconGeneral
BrandMitsubishi
Model7011A SERIES
CategoryUPS
LanguageEnglish

Related product manuals