MITSUBISHI
ELECTRIC
7011A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-4
MITSUBISHI ELECTRIC 7011A SERIES UPS
TABLE 3.2 Recommended Cable Size and Torque Requirements
UPS Capacity Input Side *1 Output Side *1
(kVA) Cable Size Torque (in. lbs) Cable Size Torque (in. lbs)
6kVA
(208V)
10 AWG *
2
or larger
80
in. lbs
10 AWG *
2
or larger
80
in. lbs
8kVA
(208V)
8 AWG *
2
or larger
80
in. lbs
8 AWG *
2
or larger
80
in. lbs
10kVA
(208V)
6 AWG *
2
or larger
80
in. lbs
6 AWG *
2
or larger
80
in. lbs
12kVA
(208V)
6 AWG *
2
or larger
80
in. lbs
6 AWG *
2
or larger
80
in. lbs
*1 - Voltage drop across power cables not to exceed 3% of nominal source voltage.
*2 - Allowable ampere ratings based on 90
°C insulation at an ambient temperature of 40 °C.
No more than 3 conductors in a raceway without de-rating. Use copper conductors rated 90
°C.
TABLE 3.3 Crimp Type Compression Lug
Wire
Size
Wire
Strand
Recommendation Crimp tool required
BUNRNDY type Y35 or Y46
(Code) Class Vendor Cat. No. Color key Die index
10 B BURNDY YAV10 T3BOX - -
8 B BURNDY YA8C-L1 BOX RED 49
6 B BURNDY YA6C-L BOX BLUE 7 / 374
NOTE: When using crimp type lugs, the lugs should be crimped to the
specifications given in the manufacturer's instructions for both
crimp tool and lug.
FIGURE 3.2 UPS Terminal Designation
Terminals:
INPUT
L1, N, L2
Terminals:
OUTPUT
L1, N, L2
Output
AC input
BATTERY
CB1
FO
FI
CONVERTER INVERTER
UPS Module
CB2
FB
52CS
Static Transfer
Switch
B+
B-
G