(13) OVER HEAT AM?.
C‘
c
c
This alarm appears if thermal protector of
FR-SFj
trips (installed on cooling fan).
Cause
Checkup
Remedy
Overload
1. Check motor for load
condi-
1. Lighten load.
tion.
2. Check motor start/stop fre- 2. Decrease
quency.
start/stop
frequency.
High ambient
temp-
Measure the ambient
tempera- If the ambient
erature
ture.
temperature is
higher than
55'C,
appropriate pro-
vision shouid be
made to cool.
Trouble with
cool-
Check if the FR-SFJ cooling
Replace the cool-
ing fan fan does not work properly.
ing fan.
Heat radiating fins Check if heat radiating fins
Clean the fins.
fouled
on the back of FR-SFJ are
fouled heavily.
Fuse blown out Check if fuse is blown out.
Replace the fuse.
If new fuse is blown out
Refer to
"Alarm
again
.
.
.
.
46".
c
-103-