6. APPLICATION OF FUNCTIONS 
6 -  36 
 
Forward
rotation
0 r/min
Reverse
rotation
Command speed
Forward
rotation
0 r/min
Reverse
rotation
Command speed
MD0
(Operation mode selection 1)
ON
OFF
ON
OFF
SON (Servo-on)
ON
OFF
ON
OFF
ON
OFF
Point table No.
Command position
Command position
«Axis 2»
ST1
(Forward rotation start)
Cam No.
CAMC
(Cam control command)
Cam axis one cycle current value
Cam axis feed current value
CAMS
(Under cam control)
ON
OFF
INP (In-position)
ON
OFF
MEND
(Travel completion)
«Axis 1/Axis 2»
«Axis 1»
5 ms or longer
3 ms or shorter
Point table No. 1
Point table No. 1
1
ST1
(Forward rotation start)
ON
OFF
0.888 ms or shorter
3 ms or shorter
1
3 ms or longer
Max. 20 ms
 
Fig. 6.7 Timing chart 
 
Input start commands simultaneously with the DI signal or serial communication from controllers 
such as programmable controllers. The start delay time of the main shaft and driven shaft is 888 µs 
at a maximum because it depends on the fetch cycle of the start signal. The detection of external 
input signals is delayed by the time set in the input filter setting of [Pr. PD29]. 
Even though CAMC turns on, the command is not reflected after ST1 turns on (during point table 
operation or JOG operation). The command is not also reflected even though CAMC turns on in the 
servo-off state. 
CAMC is determined at the on edge, not on level. Even though CAMC turns off or on before CAMS 
turns on, the command is not reflected.