7. PARAMETERS
7 - 54
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]
Control
mode
CP CL
PD34
*DOP5
Function
selection D-5
_ _ _ x Alarm code output
Select an alarm code output.
When an alarm occurs, the alarm code is outputted to CN1-23, CN1-24, and CN1-49
pins.
0: Disabled
1: Enabled
For details of the alarm codes, refer to chapter 8.
When "1" is set to this digit while MBR or ALM is assigned to CN1-23, CN1-24, or
CN1-49 pin, [AL. 37 Parameter error] will occur.
0h
_ _ x _ Selection of output device at warning occurrence
Select ALM (Malfunction) output status for a warning occurrence.
0h
Setting
value
Device status
0
OFF
ON
OFF
ON
WNG
A
LM
Warning occurrence
1
OFF
ON
OFF
ON
WNG
A
LM
Warning occurrence
_ x _ _ For manufacturer setting 0h
x _ _ _ 0h