8-504.11
TECHNICAL DATA
DX Cooling Only and Heat Pump Units - IP Units
Table 26.1 - Technical Data – DX Cooling Only and Heat Pump Units - IP Units
Model Digit 2,3 + Model Size
DESCRIPTION UNITS SD/SH 18 SD/SH 24 SD/SH 30 SD/SH 36 SD/SH 42
CAPACITY
Total Cooling Capacity (1) BTU/hr 19,200 23,000 31,400 38,200 42,500
Sensible Cooling Capacity (1) BTU/hr 15,600 18,000 27,000 30,400 33,400
Nominal Heating Capacity (2) BTU/hr 16,400 21,400 27,400 32,400 37,200
CONSTRUCTION
Material: Fascia
High Impact Polystyrene (Light Grey color), UL 94 VO Fire Rating
Material: Chassis Galvanized Steel
EVAPORATOR
Type Finned Tube
Quantity 1
Face Area ft² 4.0 5.2
Nominal Airow - H/M/L CFM 590 / 540 / 465 670 / 590 / 540 920 / 800 / 680 1000 / 920 / 800 1130 / 1000 / 920
Discharge 4-Way
FAN
Type Centrifugal
Quantity 1 2
Diameter in 14
Horsepower (per fan) HP 1/6
REFRIGERATION
Number of Circuits 1
Refrigerant Type R-410A
WEIGHTS
Weight - Chassis
lb
66 97
Weight - Fascia 18 21
CONNECTIONS
Suction (3)
in
0.75
Liquid (3) 0.375
Condensate (ID) 0.375
FILTRATION
Type Washable Polyester Foam (Standard)
Size (5) in 11.6 x 23.2 x 0.2
Type MERV 10
Nominal Size (5) in 12.0 x 25.0 x 1.0
Quantity 2 3
CONDENSATE PUMP
Maximum Head in 30
Nominal Flow-rate gpm 0.1
OPTIONS
Electric Heating Capacity kW 3.0 5.0
HW Heating Capacity (4) BTU/h 38,700 42,200 56,600 59,600 64,300
HW Coil Connection (OD) in 7/8
Max Supply Air Branch Duct
Connections
qty 2
Supply Air Branch Duct
Diameter
in 5 6
Ducted Supply Air Volume (5) CFM 115 130 180 200 220
Fresh Air Connections qty 3
Fresh Air Duct Diameter in 3
Fresh Air Volume (6) CFM 60 65 85 90 95
(1) Nominal cooling capacity based on 80/67°F (26.7/19.4°C) DB/WB and 95/75ºF (35/23.9°C) DB/WB ambient and High Speed.
(2) Nominal heating capacity based on 70/60°F (21.1/15.6°C) DB/WB and 47/43°F (8.3/6.1°C) DB/WB ambient and High Speed for Heat Pump models (Digit 3 = H)
(3) Refrigerant line sizes should always match condensing unit connection sizes.
(4) Nominal heating capacity based on 70/60°F (21.1/15.6°C) DB/WB and water temperature of 180ºF (82.2°C) inlet / 160ºF (71.1°C) outlet.
(5) Maximum air volume available through one branch duct 6 ft (1.8 m) long, with Cassette fan(s) at high speed and corresponding fascia aperture closed.
(6) Maximum fresh air through all knockouts connected to one 10 ft (3.1 m) long duct with fan at high speed. Fresh air volume will depend on duct configuration, fan speed,
and filter type.
(7) For conditions different to those shown, refer to Accuspec Breeze.