Master Operation Mode
112
05/01 AWB2700-1384GB
The following table contains all specific error information for
SFCs 65 to 74
Error code Explanations (general) Explanations (SFC-specific)
(W#16#)
0000 Processing was completed
correctetly.
SFC 69 „X_ABORT" and SFC 74
„I_ABORT":REQ = 1, and the specified
connection is not established. SFC 66
„X_RCV":EN_DT = 1 and RD = NIL
00xy SFC 66 „X_RCV" for NDA = 1 and
RD<>NILRET_VAL contains the length of the
received data block (for EN_DT=) and/or the
copied data block in RD (for EN_DT=1).
SFC 67 „X_GET":RET_VAL contains the length
of the received data block.
SFC 72 „I_GET“RET_VAL contains the length of
the received data block.
7000 SFC 65 „X_SEND", SFC 67 „X_GET",
SFC 68 „X_PUT", SFC 69 „X_ABORT",
SFC 72 „I_GET", SFC 73 „I_PUT" und
SFC 74 „I_ABORT": Aufruf mit REQ = 0 (Aufruf
ohne Bearbeitung). BUSY hat den wert 0, es ist
keine Datenübertragung aktiv.
SFC 66 „X_RCV": EN_DT = 0/1
und NDA = 0
7001 Initial call with REQ = 1: data
transmission was initiated; BUSY
has the value 1.
7002 Intermediate call; (REQ is
irrelevant):data transmission is
already active; BUSY has the
value 1.
8090 Specified target adress of the
communication is invalid, e.g.
* false IOID
* available for false base adress
* false MPI-Adresse (>126)