Digital Output Status
Indicators
81
05/01 AWB2700-1384GB
8
Digital Output
Status Indicators
16-Channel Digital Output, Positive Switching,
Short-circuit Proof
This module with short-circuit proof outputs has a lower LED row
with the LEDs RUN, BF, DIA, U
L1
, U
L2
und 1 to16.
LED State Description
RUN (green) lit Module supply voltage present (U
S
)
not lit Module supply voltage missing (U
S
)
BF (red) lit Bus-error. In the parametric monitoring time no
communication cycle took place on the bus.
not lit Communication OK
LED (green)
1 to 16
lit Signal active (voltage present)
not lit The channel is not switched or is short-circuit
LED (green)
U
L1
u. U
L2
lit Field voltage present
not lit No field voltage
LED DIA (red) lit Diagnosis: Short circuit in output or diagnosis: field voltage
(U
L1
or U
L2
) missing
not lit No error