4 Mounting Variants
Switching Cabinet
Installation
Mounting Rail
WIN
bloc eco modules must be mounted on 35 mm mounting rails
DIN/EN 50 022 35 x 15.
Mounting rails should be installed on a mounting plate (thickness
at least 2 mm) to create a reference potential for the ground
connection and screen.
Rails that are not pre-drilled should have holes drilled up to a max.
of 150 mm apart.
Location Requirements
For the installation of modules the VDE guidelines for wire-saving
transmission systems have to be considered, e.g. VDE 013 Part 1 or
EN 60204 Part 1.
X
WIN
bloc eco modules fulfil the requirements of protection type
IP 20, according to DIN 40050/IEC 144.
X
WIN
bloc eco modules have sufficient self-ventilation, i.e. no
additional ventilation is needed.
X
In the case of horizontal installation a module can be used at an
ambient temperature range between 0 to +60 °C.
X
In the case of vertical installation the heat dissipation is reduced
which means that vertically installed modules can be used at an
ambient temperature of up to +40 °C.
X
The ambient temperature should not be subjected to large
fluctuations to avoid water condensation.
X
Relative air humidity should be 15 to 90 %, without dewing.
X
Each module must be positioned at least 200 mm from potential
malfunction sources (e.g. inverted rectifiers) and high tension
lines.
X
The distance between a module-set and the cable channel
should be at least 10 mm.
Due to serious hazards, free installation is only limitedly
permitted!