Technical Data
Electronics module DP-16DO/0.5A-PK-ECO
Operating voltage (U
S
) 24 V DC
Permissible range 18 to 30 V DC
Indication LED green „RUN"
Operating current (I
S
) 70 mA
Field voltage 24 V DC
Permissible range 18 to 30 V DC
Indication LEDs green „U
L1
", „U
L2
"
Polarization protection yes
Field current (no load) 20 mA per U
L
supply
Potential separation to field bus 500 V
eff
/min
Outputs (Number) 16 (2x8) with byte-by-byte field voltage supply
I
out
Short-circuit proof yes
Output delay < 100 µs (at R
F1 k)
Synchronisation factor 100 %
Lamp load max. 3 W
Indication LED green „1-16"
Diagnosis see chapter 8
Error diagnosis via the bus yes
Short-circuit yes
Field voltage yes
Umgebungstemperatur
- Betriebstemperatur
- Lagertemperatur
- relative Feuchte
0 to +60 °C
-20 to +85 °C
15 to 95 % without dewing
Field bus
Protocol PROFIBUS DP acc. to EN 50170
Transmission rates 9,6 kBit/s to 1,5 MBit/s
EMV Interference immunity
acc. to EN 50082-1 und 2
Static electricity 8 kV air discharge,
6 kV relay discharge acc. to EN 61000-4-2
Electromagnetic fields 10 V/m acc. to ENV 50140