Technical Data
130
05/01 AWB2700-1384GB
Technical Data
Electronics module DP-32DO/0.5A-PK-ECO
Operating voltage (U
S
) 24 V DC
Permissible range 18 to 30 V DC
Indication LED green „RUN“
Operating current (I
S
) 70 mA
Field voltage 24 V DC
Permissible range 18 to 30 V DC
Indication LEDs green „U
L1
", „U
L2
" „U
L3
" and „U
L4
"
Polarization protection no
Field current (no load) 20 mA per U
L
-supply
Potential separation to field bus 500 V
eff
/min
Outputs (Number) 32 (4x8) with byte-by-
byte field voltage supply
I
out
Short-circuit proof yes
Output delay < 100 µs (at R
F1 kΩ)
Synchronisation factor 100 %
Lamp load max. 3 W
Indication LED green „1-32"
Diagnosis see chapter 8
Error diagnosis via the bus yes
Overcurrent yes
Field voltage yes
Ambient temperature
- Operating temperature
- Storage temperature
- Relative humidity
0 to +60 °C
-20 to +85 °C
15 to 95 % without dewing
Feldbus
Protokoll PROFIBUS DP acc. to EN 50170
EMC Interference immunity acc. to EN 50082-1 and 2
Static electricity 8 kV air discharge, 6 kV relay discharge
acc. to EN 61000-4-2
Electromagnetic fields 10 V/m acc. to ENV 50140
Burst 2 kV acc. to EN 61000-4-4
communication interfaces
2 kV, acc. to IEC 801-4