MGate 5111 Getting Started
Rotary Switch: PROFIBUS address 0-99 (address 100-125 supported through software configuration)
Modbus RTU/ASCII (Master/Slave)
RS-232/422/485, software selectable
Up/Down Resistor for RS-485: 1 kΩ, 150 kΩ
Modbus Serial Communication Parameters
None, Even, Odd, Space, Mark
RTS/CTS, RTS Toggle (RS-232 only)
RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
-422: Tx+, Tx-, Rx+, Rx-, GND
-485-4w: Tx+, Tx-, Rx+, Rx-, GND
-485-2w: Data +, Data -, GND
1, 2, 3, 4, 5, 6, 15, 16, 23
Max. Number of Connections:
MGate as Modbus TCP Client: 32 connections
MGate as Modbus TCP Server: 16 connections
Max. Total I/O Data Size:
Input: 2048 bytes, Output: 2048 bytes
CIP Objects Supported: Identity,
Message Router, Assembly,
Connection Manager, TCP/IP interface, Ethernet link, Port
Max. Number of Connections:
1 connection for read/write
Max. Total I/O Data Size:
Input: 496 bytes; Output: 496 bytes
Input 512 bytes/output 512 bytes
Maximum No. of Connections:
Web console, Serial console
Device Search Utility (DSU) for Windows 95, 98, ME, NT, 2000,
Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows
Server 2008 R2, Windows 7/8/8.1/10 (x86/x64), Windows Server 2012
TCP/IP, UDP, HTTP, HTTPS, SMTP, NTP, DNS,
DHCP Client, SNMP (v1, v2c, v3), MIB