2 Sensors 2023-11 Page 16 | 40
6.1 Run-in Time
Caution:
Prior to calibration, the sensors must be supplied with power voltage without interruption
for run-in and stabilisation. The run-in time depends on the sensor element and is shown
in the following tables.
A: Catalytic Sensor Element (Pellistor)
for Combustible Gases
Run-in time
calibration (h)
Table 4: Calibration Pellistor Sensor Element
B: Electrochemical Sensor
Element
for Toxic Gases and Oxygen
Calibration with
surrogate gas
(ratio surrogate
gas : gas)
Run-in time
calibration (h)
Gas application
time
2
(s)
Table 5: Calibration Electrochemical Sensor Element
C: Semiconductor
Sensor Element
Stabilisation time until
specification (min)
Run-in time
calibration
3
(h)
Table 6: Calibration Semiconductor Sensor Element
D: Infrared-
Sensor Element
Run-in time
calibration (h)
Gas application
time
2
(s)
Methane, propane, carbon dioxide, R32 (Premium sensor)
Methane, propane, carbon dioxide
Table 7: Calibration Infrared Sensor Element
1
Stainless steel housing option requires a flow rate of 500 ml/min.
2
Stainless steel housing option requires longer gas application times.
3
A run-in time of 168 h is recommended for initial commissioning.