8 Troubleshooting
8.1 Indications for the SC2
The SC2 has got no diagnostic indications; they are only available on the SB2, MSC2, MSB2 or WSB2
Board.
8.2 Indications for the MC2
The 420 mA output of the MC2 can be used as diagnostic indicators.
Output current
Device error
2 mA
Tolerable negative sensor drift
34 mA
Normal measurement mode
420 mA
Tolerable overrange
2021.2 mA
Overrange error
> 21.8 mA
Maintenance message
19 mA