D: Infrared Sensor Element for Methane, Propane, Carbon Dioxide (and R32)
Sensor Element SC2/MC2 Methane/Propane/Carbon Dioxide/R32 – Premium
1
A deviating storage temperature can have a negative effect on sensitivity and service life
2
If stocked for a longer period, we recommend checking the zero point and recalibrating if necessary.
3
Expected service life for normal ambient conditions
4
Manufacturer-recommended calibration intervals for normal environmental conditions.
5
The recommended mounting height depends on the relative gas density of the type of gas to be monitored. Depend-
ing on the relative gas density (d), the following recommendation therefore applies:
d ≤ 0.85: Mounting 0.3–0.5 m below the ceiling
0.85 < d < 1.15: Mounting at 1.2–1.8 m height
d ≥ 1.15: Mounting 0.3–0.5 m above the floor