1
A deviating storage temperature can have a negative effect on sensitivity and service life.
2
The recommended mounting height depends on the relative gas density of the type of gas to be monitored. Depend-
ing on the relative gas density (d), the following recommendation therefore applies:
d ≤ 0.85: Mounting 0.3–0.5 m below the ceiling
0.85 < d < 1.15: Mounting at 1.2–1.8 m height
d ≥ 1.15: Mounting 0.3–0.5 m above the floor
3
Due to the high amplification, the lowest reliable detection limit for Acetylene is 10 % LEL.