User Manual PolyGard
®
2 Sensors 2023-11 Page 29 | 40
Gas type
Ordering No.
Measuring range
1
Temperature range
Humidity range
non-condensing
Pressure range
Storage tempera-
ture range
2
Life time
3
in air
Relative gas den-
sity
4
Calibration inter-
val
5
SC2- /
MC2-X-
ppm
°C
% RH
kPa
°C
> years
Air = 1
Months
CO
E1110-A
050
-20 / +50
1590
90-110
10-30
2
0.97
12
CO
E1110-C
0150
-20 / +50
1095
80-120
0-20
6
0.97
12
CO
E1110-E
0250
-20 / +50
1095
80-120
0-20
6
0.97
12
CO
E1110-F
0300
-20 / +50
1095
80-120
0-20
6
0.97
12
CO
E1110-H
0500
-20 / +50
1095
80-120
0-20
6
0.97
12
NH
3
E1125-A
0100
-30 / +50
1590
80-120
0-20
2
0.60
12
NH
3
E1125-B
0300
-30 / +50
1590
80-120
0-20
2
0.60
12
NH
3
E1125-C
0500
-30 / +50
1590
80-120
0-20
2
0.60
12
NH
3
E1125-D
01000
-30 / +50
1590
80-120
0-20
2
0.60
12
NH
3
E1125-E
05000
-30 / +50
1590
90-110
0-20
2
0.60
12
NO
E1129-C
0100
-30 / +50
1590
80-120
0-20
2
1.04
12
NO
2
E1130-A
010
-30 / +50
1590
90-110
0-20
2
2.80
12
NO
2
E1130-B
020
-30 / +50
1590
80-120
0-20
2
2.80
12
NO
2
E1130-C
030
-30 / +50
1590
80-120
0-20
2
2.80
12
NO
2
E1130-E
0100
-30 / +50
1590
80-120
0-20
2
2.80
12
NO
2
E1130-F
05
-20 / +50
1590
80-120
0-20
2
2.80
12
VOC
E1160-A
010
-40 / +55
1595
80-120
0-20
3
-
12
VOC
E1160-B
05
-40 / +55
1595
80-120
0-20
3
-
12
HCN
E1183-B
050
-20 / +50
1590
90-110
5-20
2
0.93
6
HCN
E1183-C
0100
-20 / +50
1590
90-110
5-20
2
0.93
6
CH
2
O
E1185-B
010
-30 / +50
1590
90-110
5-20
3
1.04
6
HCl
E1186-D
020
-20 / +50
1590
90-110
5-20
2
1.27
6
C
2
H
4
E1189-C
0200
-30 / +50
1590
90-110
5-20
2
0.97
6
O
3
E1190-A
05
-30 / +50
1590
90-110
5-20
2
1.66
6
O
3
E1190-B
010
-30 / +50
1590
90-110
5-20
2
1.66
6
Cl
2
E1193-C
010
-30 / +50
1590
90-110
5-20
2
2.48
6
Cl
2
E1193-D
020
-30 / +50
1590
90-110
5-20
2
2.48
6
H
2
E1194-A
01000
-20 / +50
1590
90-110
10-30
2
0.07
12
SO
2
E1196-B
020
-30 / +50
1590
80-120
0-20
2
2.73
6
H
2
S
E1197-A
050
-30 / +50
1590
80-120
0-20
2
1.19
6
H
2
S
E1197-B
0100
-30 / +50
1590
80-120
0-20
2
1.19
6
H
2
S
E1197-C
0200
-30 / +50
1590
80-120
0-20
2
1.19
6
H
2
S
E1197-D
0500
-30 / +50
1590
80-120
0-20
2
1.19
6
H
2
S
E1197-E
01500
-30 / +50
1590
90-110
5-20
2
1.19
6
ETO
E1199-A
010
+10 / +30
1590
90-110
5-20
2
1.56
12
1
Exceeding the measuring range limit will include a risk of damaging the sensor element.
2
A deviating storage temperature can have a negative effect on sensitivity and service life.
3
Expected service life for normal ambient conditions
4
The recommended mounting height depends on the relative gas density of the type of gas to be monitored. Depend-
ing on the relative gas density (d), the following recommendation therefore applies:
d ≤ 0.85: Mounting 0.30.5 m below the ceiling
0.85 < d < 1.15: Mounting at 1.21.8 m height
d ≥ 1.15: Mounting 0.30.5 m above the floor
5
Manufacturer-recommended calibration intervals for normal environmental conditions.