Fault
code no. Full designation Meaning Action
Setting parame-
ter no.
365 AL Stop MV-Wiring
Ground
Injector wiring fault. Engine
stop configurable (alarm con-
figuration parameter, see PR
2.8008.100 for explanation).
Possible causes: 1. Short cir-
cuit of injector positive con-
nection to ground of one or
more injectors. 2. Short cir-
cuit of injector negative con-
nection to ground of one or
more injectors.
Check wiring, re-
place wiring harness
as necessary.
1.8004.561
381 AL Wiring TOP 1 Short circuit or wire break at
transistor output 1 plant side
(TOP 1, alarm configuration
parameter, see PR
2.8008.100 for explanation).
Check wiring. 2.8006.638
382 AL Wiring TOP 2 Short circuit or wire break at
transistor output 2 plant side
(TOP 2, alarm configuration
parameter, see PR
2.8008.100 for explanation).
Check wiring. 2.8006.639
383 AL Wiring TOP 3 Short circuit or wire break at
transistor output 3 plant side
(TOP 3, alarm configuration
parameter, see PR
2.8008.100 for explanation).
Check wiring. 2.8006.640
384 AL Wiring TOP 4 Short circuit or wire break at
transistor output 4 plant side
(TOP 4, alarm configuration
parameter, see PR
2.8008.100 for explanation).
Check wiring. 2.8006.641
390 AL MCR exceeded DBR/MCR function: MCR
(maximum continuous rate)
exceeded. Engine power is
limited to admissible continu-
ous power (alarm configura-
tion parameter, see PR
2.8008.100 for explanation).
None. 1.1085.009
400 AL Open Load Digital
Input 1
Line disruption at digital in-
put 1, wiring faulty or no re-
sistance via switch, (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Check wiring. 2.8006.625
401 AL Open Load Digital
Input 2
Line disruption at digital in-
put 2, wiring faulty or no re-
sistance via switch, (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Check wiring. 2.8006.626
MS15018/03E 2016-02 | Troubleshooting | 63
TIM-ID: 0000008508 - 003