3.11 Enabling SMS Messages
Sending SMS message requires a Communicator 2.0 having an internal modem (supplied by
Munters if ordered). This modem will support your cellular infrastructure and region (4G US, 4G
ROW, 3G)
Insert a 3G or 4G standard SIM card as indicated:
3.12 Testing the Battery
CAUTION
Munters highly recommends testing the battery immediately after completing the installation!
1. Ensure that the battery is charged (Green LED should be on continuously). If the LED blinks, wait.
2. Disconnect the AC power. Power LED turn red.
3. You should receive an alarm according to the contact list settings.
4. After receiving the alarm message, reapply power.