© Munters AB, 2019 38
3. Edit the following parameters:
o
Alarm Report Delay: To prevent you from being overloaded with insignificant alarms,
you can define the amount of time an alarm condition must continue before an alarm is
sent.
o
User Gap Time: Define the delay time (if any) between messages sent to the next person
on the list (see the Priority setting).
o
Message Repeat Delay: Alarms must be acknowledged or messages are resent to the
list. Define the amount of time in which acknowledgment must take place before
resending messages.
o
Test Message Time: A test message can be sent daily to ensure that message
transmission is operating properly. This parameter sets the time that this message is sent.
o
Country of installation: Choose from the drop down list.
o
Generator Ip Address (US customers only): Users having a backup generator
connected to the Communicator 2.0 can enter the generator’s IP address. Communicator
2.0 will transmit any alarms from the generator.