EasyManuals Logo

Munters HC-300 User Manual

Munters HC-300
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
5-3
7. There may be a problem with the thermistor which controls the solid state power
control (TSE1) See the section on “Checking the Thermistors.” There may also be
a problem with the power control itself (SSP1) Substitute a new part.
5.5 POOR DEHUMIDIFYING PERFORMANCE
1. Checkthetwointakelters,showninFig.1-4.Iftheseltersaredirty,cleanthem
asdescribedinthesectionon“CleaningtheAirFilters.”
2. Ifyouhaveinstalledbirdscreensontheintakeandoutletforthereactivationair,
check these.
3. Has something changed in the process space which could increase the moisture
load on the unit? Check all openings into the process space to be sure all doors
and windows are closed. Check for leaks in the ductwork.
4. Thevolumeofprocessairmaybetoogreat.Youcanreducethevolumeofprocess
air by closing the process damper. (The control system will sense the changing con-
ditionsinthestreamofprocessair,andmakeadjustmentstothetemperatureand
volumeofthereactivationair.)
5. Checktheairtemperatureattheoutletforthereactivationair.Itshouldbe120°F,
±5°.Ifitisnot,seethesectionon“ReactivationOutletTemperatureisTooLow.”
6. Oneormoreoftheheatingelementsmaynotbeworking.Seethesectionon
“Checking the Heating Elements.”
7. Iftheprocessblowerisoverloaded,itwillshutdownautomatically.Thiswillprevent
theunitfromdryingtheprocessair.Themotorwillrestartautomatically,onceithas
cooled.
8. The HoneyCombe
®
wheel may be stopped. See the next section.
5.6 HONEYCOMBE
®
WHEEL IS STOPPED, RUNNING LIGHT IS ON
1. Checkthewheeldrivesystem.SeeFig.1-4.Pullbackonthetensionertoloosen
thebelt.Removethebeltfromthedrivewheelonthemotor.SettheManual/Off/
AutoswitchtotheManualpositiontoturnontheunit.Thedrivemotorshouldturn
slowly.Seesection5.10,CheckingtheDriveMotor,WheelandSeals.
2. Afterlonguse,thelowersealmaywear.TheHoneyCombe
®
wheel will then ride on
theinnerlayerofthesealmaterial.Sincethisisnotasslipperyastheouterlayer,
the wheel will not turn easily. Check the condition of the lower seal. The surface of
thesealshouldbesmooth.Ifthesealisveryworn,youwillbeabletoseesomeof
theinnerlayerofsealmaterial.Ifthesealmustbereplaced,pleasecontactthefac-
tory for instructions.