®Munters
5.5 Start the unit
The
unit is stopped and started using the
mode
switch, see
Figure
5.
4.
0:
Theunitis
switched off.
AUTO:
The
supply air fan runs continuously. All functions in the unit are controlled
in
proportion
to
the existing need.
1.
Make sure that
all
supplies
of
electricity and
hot/
cold water are
on
and functional.
2.
Set the main power switch to 1 (On).
3.
Set the
mode
switch
on
the operation panel
to
AUTO.
5.6 Stop the unit
When
the unit is stopped
all
the functions
in
it are stopped apart from freeze monitoring.
To stop the unit, set the
mode
switch
on
the operation panel to
0.
LL
CAUTION!
In
order
to
dissipate any residual heat, the fans and the drive motor continue
to
run
( after
the
unit
is
switched off)
until
the
temperature falls below
50
°C
.
Do
not turn off the main power before the fans have come
to
a complete
stop.
Close the
cold/hot
water shut-off valves for the cooling and heating coil(
s).
5.
7 Quick stop
The
unit can
in
an emergency
be
stopped using the main power switch, see section 5.
1,
Main
power
switch.
LL
CAUTION!
Only
use
the
main power switch
to
stop the unit
in
the
case
of
an
emergency.
The
normal shutdown sequence will
not
be
followed.
The
fans
stop and the heater
can
be very
hot,
which can result
in
damage
to
the heater and other
components close
to
it.