4.4.1.2 Configuring the Munters Drive fans
Connect the analog output devices (Munters Drive) as shown in Figure 6.
Connect fans 1, 2, or 3 as shown in Figure 7 (optional).
1. Press
.
2. Scroll to Settings and press
.
3. Scroll to Fan 1 and press
.
4. Set the following parameters:
o
: The differential from the target temperature at which the fan turns on
o
: When the fan begins to operate, the fan goes from the minimum to
maximum operation percentages within this band.
o
: Beginning of the time period in which the fans can operate
o
: End of the time period in which the fans can operate
NOTE Setting the time from 00:00 to 00:00 enables 24 hour operation. Setting
other
identical times (for example 13:15 to 13:15) disables the fans.
o
: Minimum fan speed in percentages.
o
: Maximum fan speed in percentages
5. Press
.
6. Scroll to Fan 2 and Fan 3 and press
.
7. Repeat step 4.
8. Press
and then press
.
9. Scroll to Calibration and press
.
10. Scroll to Fan 1 Min Volt.
11. Set the minimum possible voltage for the fan.
12. Press
.
13. Scroll to Fan 1 Max Volt.
14. Set the maximum possible voltage for the fan.
15. Repeat for each fan.
4.4.2 Foggers and soakers
The following section details how to configure the foggers and soakers. These work in conjunction
with the Munters Drive Fans. Soakers work with Munters Drive 1, foggers work with Munters
Drive 2.
•
Fogger and soaker background
•
Configuring the fogger and soaker
4.4.2.1 Fogger and soaker background
Figure 3 illustrates a sample graph showing how soakers (sprinklers) and ventilation work together.
Figure 4 illustrates a sample graph showing how soakers (sprinklers) and fogging work together