Section 40 00-02-0994
2016-06-28 - 36 -
Coolant Temp (0-5V) or (4-20mA)
Discharge Pressure (0-5V) or (4-20mA)
Fluid Pressure (0-5V) or (4-20mA)
Fuel Level (0-5V) or (4-20mA)
Oil Temp (0-5V) or (4-20mA)
Pump Housing Temp (0-5V) or (4-20mA)
Pump Oil Temp (0-5V) or (4-20mA)
Suction Pressure (0-5V) or (4-20mA) By raising the minimum value (5mA or 1V) in the sensor
setup, a negative Suction Pressure can be read by the Controller.
Flow Rate (4-20mA)
Speed (4-20mA)
System Level (4-20mA)
Set mA per Ft
Relay (1-6) and Digital (1-6) Outputs: these same parameters are used for both the Relay and Digital Outputs.
Relay 1. Factory set to Crank
Relay 2. Factory set to ECU Enable. The controller will not transmit on the CAN bus when this output is
off
Relay 3. Factory set to Common Alarm
Relay 4. Factory set to Shutdown
Relay 5. Factory set to At Load (Clutch)
Relay 6. Factory set to Prestart 1 Delay
DO1 (5V, 200mA). Factory set to Not Used
DO2 (5V, 200mA). Factory set to Not Used
DO3 (B+, 2A) Factory set to Not In Auto
DO4 (B+, 2A). Factory set to Engine Running
DO5 (B-, 1A). Factory set to ECU Diagnostic Mode
DO6 (B-, 1A). Factory set to Clear ECU Fault Codes
Not Used
Prestart Delay 1 Please see Timers on page 30.
Prestart Delay 2 Please see Timers on page 30.
Crank Please see Timers on page 30.
Fuel Please see Timers on page 30.
ECU Enable Used for enabling the ECU on electronic engines. This output is on any time the
controller is powered up or in the crank/run state. It’s turned off if the controller is in the standby
state.
Excite Engine Alternator Used for alternators requiring excite from battery. This output is turned
on in the crank/run state.
At Load (Clutch) This output is turned on when the warm-up delay has expired and the engine
reaches the clutch engage RPM set point. It is turned off during the cool-down delay and the
engine reaches the clutch disengage RPM set point.
Gov. Control This output turns on after the warm-up delay expires and turns off when the cool-
down delay begins timing.
Shutdown This output turns on when a fault shutdown occurs.
Common Alarm This output turns on when either a shut-down or a non shut-down warning
occurs.
Remote Alarm This output turns on when a either a shut-down or a non shut-down warning
occurs.
Air Damper N/De-energized This output turns off during the energize to stop delay.
Not in Auto This output turns on when the controller is in the manual mode.
Air Damper N/Energized This output turns on during the energize to stop delay.
Energize to Stop Please see Timers on page 30.
Engine Running
This output turns on after the engine actually starts and off when the engine stops.