Adjustment Procedures 5-20
U30 Microprocessor Control www.NabcoEntrances.com
Part #15-9000-30 Rev. 3-12-13
Special Funcon Adjustment
Adjustment Descripon
Auxiliary Output 1
then: Output Timer 1
● Select Power Reset to cancel the error message.
● The Strike releases for (3) seconds then re-engages.
One Message will read: AUX. OUTPUT 1
The air lock opon will instruct the relay to close to prevent a second door from opening
unl the rst door is closed, in a passageway situaon.
Two Message will read: AUX. OUTPUT TIMER 2
● The sequenal door operaon opon will instruct the relay to close thereby acvang
a second Slide door for a set me period. It requires selecng the me delay between
the rst and second Slide door operaons.
● The following (4) sub-opons are available:
Zero 2 seconds
One 4 seconds
Two 6 seconds
Three 8 seconds
Three Message will read: AUX. OUTPUT 3
● A Relay Signal indicang a fully closed posion will be provided.
● Used by the Gyro Tech Access Control Panel or other similar security controls.
Extended Time Delay Message will read: EXT. TIME DELAY 7
● Enables an extended me delay beyond the 0 to7 seconds standard me delay that was set in
the Standard Funcon Adjustments program.
● Time delay is measured aer the loss of the acvaon signal.
● The following (7) opons are available:
Zero Standard 0 to 7 second delay
One 10 seconds longer than standard (10-17 seconds)
Two 20 seconds longer (20-27 seconds)
Three 30 seconds longer (30-37 seconds)
Four 40 seconds longer (40-47 seconds)
Five 50 seconds longer (50-57 seconds)
Six 60 seconds longer (60-67 seconds)
Seven Slide door will open to the full open point before closing even if the me delay has
expired during the opening cycle. The standard me delay of 0 to 7 seconds applies aer
the door reaches the open posion.