EasyManua.ls Logo

National Instruments NI 6323 - Chapter 8 PFI

National Instruments NI 6323
299 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© National Instruments 8-1 X Series User Manual
8
PFI
X Series devices have up to 16 Programmable Function Interface (PFI)
signals. In addition, X Series devices have up to 32 lines of bidirectional
DIO signals.
Each PFI can be individually configured as the following:
A static digital input
A static digital output
A timing input signal for AI, AO, DI, DO, or counter/timer functions
A timing output signal from AI, AO, DI, DO, or counter/timer
functions
Each PFI input also has a programmable debouncing filter. Figure 8-1
shows the circuitry of one PFI line. Each PFI line is similar.
Figure 8-1. X Series PFI Circuitry
Timing Signals
Direction
Control
I/O Protection
Weak Pull-Down
PFI x/P1/P2
Static DO
Buffer
To Input Timing
Signal Selectors
PFI
Filters
Static DI
PFI
Change
Detection
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Related product manuals