EasyManua.ls Logo

National Instruments PCI E Series - Page 98

National Instruments PCI E Series
162 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Programming
©
National Instruments Corporation 4-35 PCI E Series RLPM
6. Call MSC_Clock_Configure to program the timebase options.
Clock_and_FOUT_Register = 0x1B00;
7. Call
AO_Reset_All to program the timebase options.
Joint_Reset_Register
AO configuration start = 1;
AO_Command_1_Register
AO disarm = 1;
Interrupt_B_Enable_Register = 0x0000;
AO_Personal_Register
AO BC source select = 1;
Interrupt_B_Ack_Register = 0x3F98;
Joint_Reset_Register
AO configuration start = 0;
AO configuration end = 1;
8. Call
AO_Board_Personalize to configure the DAQ-STC for the
MIO board. Use the following bitfield settings:
Joint_Reset_Register
AO_Configuration_Start = 1;
If (Board Type = PCI-MIO-16E-1, PCI-6071E or PCI-MIO-16E-4)
AO_Personal_Register = 0x1410;
Else
AO_Personal_Register = 0x1430;
Clock_and_FOUT_Register = 0x1B20;
AO_Output_Control_Register = 0x0000;
AO_START_Select_Register = 0x 0000;
Joint_Reset_Register
AO configuration start = 0;
AO configuration end = 1;
9. Call
AO_Triggering to program the trigger signal. Configure the
DAQ-STC to trigger once and use a software START1 trigger.
Joint_Reset_Register
AO configuration start = 1;
AO_Mode_1_Register
AO trigger once = 1;

Table of Contents

Related product manuals