HV Control Panel
27
EN
EmptyingdoesnotstartiftheaccumulatedrunmehasnotpassedInterval1.Butifthe
MainlterDPShasindicatedahighdP(fortheResponseme,asforInterval2),then
cleaningstartsatthefollowingPilotsignaldeacvaon.
6.6.7 Emptying rotary valve
Rotary valve Range Default Used
Runme 0-999 s 30
Pause-me1 0-999 s 120
Pause-me2 0-9999 m 30
Pause-me2delay 0-99 s 30
Pause2byLI Yes/No No
Runmeisthemethevalverotates.
Pauseme1isthemethevalveisstopped.
Pauseme=0meansthevalverotatesconnually.
Outputtomotorcontactorisconnuous(Pause=0)orintermient/twointervals
controlledbyLI(levelindicator).
OperaonwhenVacuummotorisinRunningmode(oridling).
Input“Ready”formotoroverloadrelay(closewhenOK)andinserialwithmaintenance
switch(closedwhenON).
Inputrotaondetector(Pulses/min).
Levelindicatorabove(closedsignalwhenlowlevel).
Therearetwomodes:
1. Timecontrolisthedefaultmode,thenRun/Pause1/Runetc.IfLIindicateshighthen
Pause2(normallysettoashorterme).ReturntoPause1aertwoRunperiods
withoutLIindicaonhighlevel.SupervisionbyLIandWarningandAlarmdelay.
2. Levelcontrol.Thepurposeoflevelcontrolistomaintainadustlevelabovethe
valve.ItstartstoRunaerPause1andstopswhenLIindicatesalowlevel.IfLInever
indicatesalowlevel,eitherduetocoveredsensor,orbridgingsothedustisnotfed
out,thesupervisionismadebytheLIandtheWarningandAlarmdelay.
EmptyingisalsopossiblewhenmanuallyiniatedinOFFandStandbymode,i.e.,no
vacuum.