HV Control PanelEN
40
10 Remote Standby/O/Overme
Thisinput(I0.6,terminals5-6)hascombinedfunconality.
Ifthisinputisnotusedasaremotecontrol,itmustbelinked(acve).ThenOFF/Standbyis
controlledfromHMIbuonsandweekmer.
Control from superior system / machine / manual twist buon is maintained
IfWeekmerorTimerisnotenabled,theinputcanbeusedasasimpleOFF/Standby:At
acvaon(posiveedge),itgoestoStandby.Ifitismaintainedacve,thesystemstaysin
Standbymode.Atdeacvaon,signalinacve,thesystemgoestoOFFsupersedingother
startsignals.Startisinhibitedbyremote.
Remote control weekmer/overme
WithWeekmerandOverme/Timer,theinputisusedforremotecontrolofWeekmer
andforrequesngOverme.
AtwistbuonOFF-ON+Time(springback)isrecommended.Awhiteindicaonlampfrom
outputforOn/Standbylamp(Q1.1/K18,terminals89-90),isusedasanindicaon.
Thelampindicatesthestatus“Standby”byaxedlight.(RunningwhenpilotacveorSSR
counng).Italsoindicatesanalarmby1Hzblinking.Startisinhibitedbyremote.
WhenswitchedtoOFF(deacvaonofinput),statusiswitha5seconddelay,andthenitis
settoOFF.AtturntoON(acvaon),itwillcheckforWeekmerperiod.Ifthereisanacve
period,thenitissettoStandby,ifnotinacvestatus,itissllOFF.
FromposionON,ashorttwistto+TimeisanOverme/Timerrequestandisindicatedby
aburstoflampblinks.IfinanacveWeekmerperiod,Overmeisinawaingstate,and
isindicatedbythelampmakingablinkingevery5seconds.IntheHMI,theOverme/Timer
buonislightgreen.
DuringanacveWeekmerperiod,i.e.,inawaingstate,anacveOvermerequestis
indicatedbythelampblinkingevery5seconds.
TodeacvatetheOvermerequest,makeanewtwistto2secondswhichwillbefollowed
byaburstofblinksasconrmaon.
IfthereisnoacveOvermerequest,thelampwillhavexedlightwithoutblinkingevery
5seconds.Seealso. Enable Timer/Overme.
TostopandresetanacveOvermeperiod(outsideanyWeekmerperiod),switchto
OFFformorethan5secondsandthenswitchtoONagaininordertobepreparedforthe
Weekmercontrol.OrpresstheStopbuonontheHVControlPanelEX.
11 FlexFilter 13/18 with DFC-08M
DFC-08M-24VDCispowersuppliedbytheHVControlPanelEX.
Startsignaltotheunitwillusethe“Run”,seeterminal17-18intheelectricaldiagram.
AlarmsignalfromDFC-08MwillbeconnectedtoIO.5,49-50.ConguredinMACRO.See
secon6.10. System setup: MACRO.
ThealarmsignalgeneratesawarningintheHVControlPanelEXandaerthealarmdelay,
itgeneratesanalarmandstops.