4.4.2 Technical data
Table4-3:HVControlPanelEX37kW
Item Descripon
ShortCircuitCurrentRangs 25kA
ControlVoltage 24 VAC 6A /24 VDC 5 A
Maxinstallaonambienttemperature Min0°C(32°F)-Max40°C(104°F).Indooruseonly.
Proteconcategory IP 65
Motor size (kW) Supply Voltage (V) Aprox
Motor Current (A)
(I -Nominal)
Hz Recomended
Main Fuse (A)
Motor Overload seng
(A)
18,5-22 230 56-66 50/60 80
0,58*I-Nominal
18,5-37 380 34-70 50/60 50-100 0,58*I-Nominal
18,5-37 400 32-64 50 50-100 0,58*I-Nominal
18,5-37 460 28-56 60 40-80 0,58*I-Nominal
Table4-4:HVControlPanelEX45kW
Item Descripon
ShortCircuitCurrentRangs 30kA
ControlVoltage 24 VAC 14A /24 VDC 5 A
Maxinstallaonambienttemperature Min0°C(32°F)-Max40°C(104°F).Indooruseonly.
Proteconcategory IP 65
Motor size (kW) Supply Voltage (V) Aprox
Motor Current (A)
(I -Nominal)
Hz Recomended
Main Fuse (A)
Motor Overload seng
(A)
30 230 90 50 100
0,58*I-Nominal
18,5-37 380 34-70 50 50-100 0,58*I-Nominal
18,5-37 400 32-64 50/60 50-100 0,58*I-Nominal
18,5-37 460 28-56 50 40-80 0,58*I-Nominal
Table4-5:HVControlPanelEX55kW
Item Descripon
ShortCircuitCurrentRangs 30kA
ControlVoltage 24 VAC 14 A /24 VDC 5 A
Maxinstallaonambienttemperature Min0°C(32°F)-Max40°C(104°F).Indooruseonly.
Proteconcategory IP 65
Motor size (kW) Supply Voltage (V) Aprox
Motor Current (A)
(I -Nominal)
Hz Recomended
Main Fuse (A)
Motor Overload seng
(A)
30 230 90 50 100
0,58*I-Nominal
45-55 380 82-100 50/60 100-125 0,58*I-Nominal
45-55 400 78-95 50 100-160 0,58*I-Nominal