Dockings
General
NIBE SPLIT can be connected in several different ways,
some of which are shown on the following pages. For more
detailed docking descriptions, see www.nibe.eu.
Installation requirements
AMS 10-16
0.25 MPa (2.5 Bar)Max pressure, climate system
+65 °CMax temperature, climate system
+65 °CMax temperature in HBS 16
+65 °CMax temperature from external heat source
+58 °CMax flow line temperature with compressor
+7°C/+18°CMin supply temperature cooling, HBS11-16/HBS 10-16
+25 °CMax supply temp. cooling
150 lMin volume, climate system during heating, cooling*
150 lMin volume, climate system during under floor cooling*
0.79 l/sMax flow, climate system
0.39 l/sMin flow, climate system, at 100% circulation pump speed (defrost flow)
0.24 l/sMin flow, heating system
0.32 l/sMin flow, cooling system
HEV 500HEV 300Docking external addition
9–27 kWOutput external addition
0.17–0.33 l/sRecommended docking flow
* Regards circulating volume.
External circulation pump must be used when the pressure drop in the system is greater than the available external pressure.
In such cases, a bypass line with non-return valve must be installed.
Overflow valve must be used if min. system flow cannot be guaranteed.
Symbol key
MeaningSymbol
Venting valve
Shut-off valve
Non-return valve
Control valve
Safety valve
Temperature sensor
Expansion vessel
Pressure gauge
P
Circulation pump
Shunt / shuttle valve
Fan
NIBE™ SPLIT26