AMS 10-16Outdoor module
Gas pipe: OD15.88 (5/8")Dimensions, refrigerant pipe
Liquid pipe: OD9.52 (3/8")
FlarePipe connections
064 035Part no.
*If the length of the refrigerant pipes exceeds 15 m extra refrigerant must be filled at 0.06 kg/m.
Performance, HBS 16 and AMS 10-16
MaxNominalMinOutd. temp: / Supply
temp.
Heating
15.82/3.89/4.0712.02/2.71/4.443.66/0.95/3.867/35 °C (floor)
EN14511 ΔT5K Output/input/COP
10.82/3.20/3.3810.12/2.74/3.692.98/0.97/3.082/35 °C (floor)
10.09/3.54/2.858.08/2.69/3.012.72/1.18/2.30-7/35 °C (floor)
7.99/3.29/2.436.34/2.60/2.442.92/1.44/2.02-15/35 °C (floor)
15.20/4.37/3.4811.69/3.56/3.285.09/1.51/3.387/45 °C
12.18/4.40/2.779.53/3.21/2.974.10/1.48/2.772/45 °C
10.05/4.37/2.307.49/3.11/2.413.08/1.56/1.97-7/45 °C
7.50/4.00/1.885.52/2.93/1.882.72/1.68/1.61-15/45 °C
13.29/5.28/2.5210.31/3.86/2.676.55/2.38/2.767/55 °C
7.83/4.50/1.746.26/3.55/1.763.74/2.33/1.61-7/55 °C
MaxNominalMinOutd. temp: / Supply
temp.
Cooling
18.5/4.26/4.3515.0/338/4.425.80/160/4.2027/18 °C
EN14511 ΔT5K Output/input/EER
16.6/4.78/3.4713.5/3.82/3.525.20/1.79/3.4135/18 °C
91NIBE™ SPLIT
Miscellaneous
Technical specifications

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe AMS 10-16 and is the answer not in the manual?

Nibe AMS 10-16 Specifications

General IconGeneral
BrandNibe
ModelAMS 10-16
CategoryHeat Pump
LanguageEnglish

Related product manuals