11PELLUX 100/20 TOUCH
PELLUX 100/30 TOUCH
EN
Main Menu Operation
Boiler
Heating
Burner
Controller Statuses
The BOILER submenu presents the current set boiler
temperature, preset programme and operating mode.
After pressing the SETTINGS button, you enter the fol-
lowing boiler settings:
• Set temperature [�C]- temperature you want to
get on the boiler; modulation between 60-80 ºC.
• Histeresis on [�C] - temperature, to which the
temperature set point must drop, so that the boil-
er can start working again; modulation between
0-20 ºC.
• Histeresis off [�C] - temperature, of which the
temperature set point must be exceeded, so that
the boiler will stop working; modulation between
0-20 ºC.
The HEATING submenu presents the current central
heating temperature set point, preset programme and
operating mode. After pressing the SETTINGS but-
ton, you enter the following CH settings:
• Comfort temperature [�C] - room temperature
set point within the comfort range, in the Time
mode or in the Comfort mode.
• Economical temperature [�C] - room tempera-
ture set point within the economic range, in the
Time mode or in the Economic mode .
• Histeresis [�C] - Accuracy of maintaining the
room temperature set point. It can also affect the
boiler activation frequency. The burner switches
ON less frequently at higher hysteresis.
• Room sensor calib. [�C] - enables correction in
case of incorrect indication, basing on the refer-
ence thermometer.
• Work mode - selected operating mode of the cir-
cuit.
• HC temp. set manually [�C] - system tempera-
ture set point, when weather control is not used.
The BURNER submenu presents the current operating
status of the burner, the brightness of the photocell and
the number of revolutions per minute. After pressing
the SETTINGS button, you enter the following burner
settings:
• Air correction [%] - allows correction of the preset
amount of air supplied to the combustion process.
• Min power [%] - bottom limitation of the burner
power modulation range.
• Max power [%] - upper limitation of the burner
power modulation range.
After selecting the MENU button on the boiler controller
main screen, you get access to the following functions:
• Boiler
• Burner
• Heating
• DHW
• Solar heating (requires extension module)
• Buffer
• Alarm history
• Menu level (PIN)
• Software info
STATUS DESCRIPTION
TURNED OFF
The burner is deactivated. Lack of consent for
its operation.
CLEANING
Cleaning of the burner with a strong air
stream and grate ejection.
FIRING UP
Lighting up of fuel. Administration of the initial fuel
dose and launching the igniter and the blower.
INCANDESCING
Once the ame is detected in the ring up phase,
the blower speed increases to incandesce the fur-
nace.
MODULATION
The burner operates with modulated power
(power range).
BURNING OFF
Extinguishing of the furnace. Blower oper-
ates until the ame disappears.
STOP
The burner is deactivated, but there is agree-
ment for its operation. The required boiler
temperature has been reached.
Return
Return
Circulating
pump
Settings
Settings
Schedule
Photocell
Operating
mode
RPM
Current temperature
Status
Return
Circulating
pump
Mixing valve
Settings
Schedule
Operating
mode
Current temp.
on the boiler
Current CH
temp.
CH temp
Set manually
Section 5 | First Start-Up & Operation of the Boiler