18 PELLUX 100/20 TOUCH
PELLUX 100/30 TOUCH
EN
8 Technical Specications
Pellux 100 boiler
PBMAX burners
Technical parameters Unit PBMAX 20.1 PBMAX 30
Burner capacity kW 6 ÷ 20 kW 9 ÷ 30 kW
Fuel mm
Ø 6 ÷ 10 / max. length 30
Power supply V 1/N/PE 230 V, 50 Hz
Electric power W
40
Electric power at start-up W
650
Degree of protection -
IP 21
Net weight kg
14,5 17
Technical parameters Unit
PELLUX 100/20
(K-PAA 20)
PELLUX 100/30
(K-PAA 30)
Boiler class - 5 5
Rated power kW 20 30
Net weight kg 202 245
Water capacity l 60 70
Power supply V 1/N/PE 230 V, 50 Hz
Boiler efciency % 90 - 92
Boiler temperature range °C 60-80
Operating temp max °C 85
Return temp min (at the boiler inlet) °C 45
Flue gas temp °C 80 ÷ 150
Noise level dB 48 dB
Outlet mm ø127
Pressure max MPa (bar) 0.25 (2.5)
Flue gas draught required Pa 18 ÷ 20 20 ÷ 40
Length of combustion chamber mm 320 mm
Degree of protection - IP 21
Chimney diameter mm 130-160
Chimney height (recommended) m 7 m 8 m
Power consumption in standby mode W 13 W
Power consumption at nominal power W 43 W 54 W
Power consumption at min power W 20 W 26 W
Flue gas mass ow – at rated power kg/h 42 kg/h 64 kg/h
Flue gas mass ow – at min power kg/h 18 kg/h 28 kg/h
Pressure drop at the boiler – Δ10 °C mbar 2
(1)
mbar 6
(2)
mbar
Pressure drop at the boiler – Δ20 °C mbar 6
(3)
mbar 17
(4)
mbar
(1) at Q = 0,8 m3/h, (2) at Q = 1,3 m3/h, (3) at Q = 1,6 m3/h, (4) at Q = 2,5 m3/h
Chapter 8 | Technical Specications