MENU 5.3.8 - HOT WATER COMFORT
activating the mixing valve
Setting range: on/off
Factory setting: off
outgoing hot water
Setting range: 40 - 65 °C
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 – 10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Make settings for the hot water comfort here.
See the accessory installation instructions for function
description.
activating the mixing valve: Activated if mixer valve is
installed and it is to be controlled from VVM 320. When
the option is active, you can set the outgoing hot water
temperature, shunt amplification and shunt waiting time
for the mixer valve.
outgoing hot water: Here, you can set the temperature
at which the mixer valve is to restrict hot water from
the water heater.
MENU 5.3.11 - MODBUS
address
Factory setting: address 1
word swap
Factory setting: not activated
As from Modbus 40 version 10, the address can be set
between 1 - 247. Earlier versions have a fixed address
(address 1).
If you select "word swap", you will get "word swap" in-
stead of the preset standard "big endian".
See the accessory installation instructions for function
description.
MENY 5.3.12 - EXHAUST/SUPPLY AIR
MODULE
lowest extract air temp.
Setting range: 0 – 10 °C
Default value: 5 °C
bypass at excess temperature
Setting range: 2 – 10 °C
Default value: 4 °C
bypass during heating
Setting range: on/off
Factory setting: off
cut-out value, exh. air temp.
Setting range: 5 – 30 °C
Default value: 25 °C
months btwn filter alarms
Setting range: 1 – 24
Default value: 3
lowest extract air temp.: Set the minimum extract air
temperature to prevent the heat exchanger freezing.
bypass at excess temperature: If a room sensor is in-
stalled, set the excess temperature at which the bypass
damper is to open here.
months btwn filter alarms: Set how often the filter alarm
is to be displayed.
See the installation instructions for ERS for function
description.
MENU 5.3.15 - GBM COMMUNICATION
MODULE
start diff additional heat
Setting range: 10 – 2,000 DM
Factory setting: 400 DM
hysteresis
Setting range: 10 – 2,000 DM
Factory setting: 100 DM
Make settings for the gas boiler GBM 10-15 here. For
example . you can select when the gas boiler is to start.
See the accessory installation instructions for a descrip-
tion of function.
NIBE VVM 320Chapter 8 | Control - Menus58