Unidrive M/HS Frame 5 to 6 Power Installation Guide 99
Issue Number: 9
Safety information Product information Mechanical installation Electrical installation
Technical data
UL listing information
5.1.23 Braking resistor values
Table 5-25 Minimum resistance values and peak power rating for the braking resistor at
40 °C (104 °F)
Model
Minimum resistance *
Instantaneous power
rating
Continuous power
rating
kW kW
200 V
05200250 19 8.9 8.6
06200330
10 16.9
12.6
06200440 16.4
400 V
05400270 38 17.8 16.2
05400300 22 30.8 19.6
06400350
20 33.8
21.6
06400420 25
06400470 32.7
575 V
05500030
80 12.1
2.6
05500040 4.6
05500069 6.5
06500100
15 64.1
8.7
06500150 12.3
06500190 16.3
06500230 19.9
06500290 24.2
06500350 31.7
* Resistor tolerance: ±10 %. The minimum resistance specified are for stand-alone drive systems
only. If the drive is to be used as part of a common DC bus system different values may be
required. Contact the supplier of the drive for more information.