F600 Step By Step Guide 34
Additional Information
Restoring drive defaults
The drive can be restored to the original factory settings by following the procedure below:
1. Ensure the drive is not enabled.
2. Select either 50Hz defs or 60Hz defs as appropriate in Pr 00.000.
3. Press the red reset button.
Basic parameters range and default
For information on the full list of Menu 0 parameters please refer to the F600 User Guide.
Parameter Range Default
Description OL RFC-A RFC-S OL RFC-A RFC-S
00.001
Menu access
level
11.044
Menu 0 (0), All Menus (1), Read only Menu
0 (2), Read only (3), Status Only (4), No
Access (5)
00.002
Parameter
cloning
11.042
None (0), Load File 1 (1), Save File 1 (2),
Auto (3), Boot (4)
None (0)
00.003 0.000
00.004 Motor type 29.157 Induction (0), Permanent magnet (1) Induction (0)
Permanent-
magnet (1)
00.005
Volts per 1000
rpm
5.033 Rated Frequency
0 V to
1000 V
98 V
00.006 Rated current 5.007
VM_RATED_CURRENT[MIN] to
VM_RATED_CURRENT[MAX] A
VM_RATED_CURRENT[MAX]
00.007 Rated speed 5.008 0 to 35940 rpm 0.00 to 33000.00 rpm
Std: 50 Hz:
US:60 Hz:
Std:
1450 rpm
US:
1750 rpm
Std:
1500 rpm
US:
1800 rpm
00.008 Rated voltage 5.009
VM_AC_VOLTAGE_SET[MIN] to
VM_AC_VOLTAGE_SET[MAX] V
200V drive: 230 V
400V drive 50Hz: 400 V
400V drive 60Hz: 460 V
575V drive: 575 V
690V drive: 690 V
00.009
(Not
RFC-S)
Rated power
factor
5.010 0.000 to 1.000 0.85
00.010
Number or
motor poles
5.011 Automatic (0) to 480 (240) Poles Automatic (0) Poles
00.011
(Not
RFC-S)
Low frequency
voltage boost
5.015 0.0 to 25.0 % 1.0 %
00.012
(OL only)
Low load
power saving
5.013
OFF (0) or ON
(1)
ON (1) OFF (0)
00.013
(RFC
modes
only)
Autotune 5.012
None (0),
Basic (1),
Improved
(2)
None (0)
Stationary(1)
Full
Stationary(5)
None (0)
00.014
(RFC-S
mode
only)
RFC low
speed mode
5.064
Injection (0), Current (1), Current (2),
Current No Test (3), Current Step (4),
Current Only (5)
Current (2)
00.015
(RFC-S
mode
only)
Low speed
sensor-less
mode current
5.071 0.0 to 1000.0 % 100.0 %
00.016
Symmetrical
current limit
4.007
VM_MOTOR1_CURRENT_LIMIT[MIN] to
VM_MOTOR1_CURRENT_LIMIT[MAX] %
110.0 %
OFF
Reset