May be subject to change page 24 of 27
Temp. control
In the ”Temp. control” menu it is possible to set the highest and lowest inlet temperature.
” ” indicates that the menu point flashes and can be set to another value.
Use of t he CTS 600 panel :
- pr ess ESC t o go one st ep back i n t he menu
- pr ess qpt o move up or down i n a menu or t o
adj ust an act i vat ed menu
- pr ess ENTER t o act i vat e a menu
- pr ess ENTER t o conf i r m a menu
- pr ess OFF t o t ur n of f t he uni t
- pr ess ON t o t ur n t he uni t on
Cooling via compressor is
allowed at outdoor
temperatures higher than
the preset value.
Can be set from 14-22°C
WINTER
”MIN 16°C”
ENTER
SUMMER
”MIN 14°C”
Cooling via compressor is
allowed at outdoor
temperatures higher than
the preset value.
Can be set from 10-16°C
TEMP.
CONTROL
ENTER ENTER
ENTER
SUMMER
MAX ”22°C”
Lowest out-door temperature in
order for the unit to operate
according to summer temperatures.
WINTER
MAX ”24°C”
ENTER
ENTER
SUMMER
12°C”
Highest possible inlet temperature in
winter.
Can be set from 22-50 °C.
Highest possible inlet temperature in
summer.
Can be set from 16-25 °C.
These are only
shown in the panel
if the unit has a
heating surface.
Figure 18: The ”Temp. control” menu