NORDAC FLEX (SK 200E ... SK 235E)Users Manual for Frequency Inverters
244 BU 0200 en-3118
Device type SK 2xxE…
-551-323- -751-323- -112-323-
Size
4 4 4
Nominal motor power
(4-pole standard motor)
230 V
5.5 kW
7.5 kW
11.0 kW
240 V
7 ½ hp
10 hp
15 hp
Mains voltage
230 V
3 AC 200 … 240 V,
±
10 %, 47 … 63 Hz
Input current
rms
1)
23.5 A
29.5 A
40.5 A
FLA
2)
22.5 A
28.5 A
39.5 A
Output voltage
230 V
3 AC 0 … Mains voltage
Output current
3), 4)
rms
1)
23.0 A
29.0 A
40.0 A
FLA
motor mounting
2)
22.0 A
28.0 A
39.0 A
FLA
wall mounting
2)
22.0 A
28.0 A
39.0 A
Min. brake resistance
Accessories
30
20
15
Motor mounting (fan cooling 5), integrated in device)
4)
Max. continuous power / max. continuous current
S1-40°C
5.5kW / 23.0A 7.5kW / 29.0A 11.0kW / 40.0A
Max. permissible ambient temp. with nominal output current
S1
S3 70 % ED 10 min
S6 70 % ED 10 min (100 % / 20 % Mn)
40°C
50°C
47°C
40°C
50°C
50°C
40°C
44°C
44°C
Wall mounting (fan cooling 5), integrated in device)
4)
Max. continuous power / max. continuous current
S1-40°C
5.5kW / 23.0A 7.5kW / 29.0A 11.0kW / 40.0A
Max. permissible ambient temp. with nominal output current
S1
S3 70 % ED 10 min
S6 70 % ED 10 min (100 % / 20 % Mn)
45°C
50°C
50°C
45°C
50°C
50°C
45°C
47°C
47°C
General fuses (AC) (recommended)
slow-blowing
35 A
50 A
50 A
Isc
6)
[A]
UL fuses (AC) permitted
Class
10 000
65 000
100 000
Fuse
CC, J, R, T, G, L (300 V)
x 60 A 60 A 60 A
CB
7)
(300 V ) x
60 A 60 A 60 A
1) Note derating curve ( Section 8.4.4 "Reduced output current due to mains voltage").
2) FLA Full Load Current, maximum current for the entire mains voltage range as stated above (200 V 240 V) according to UL/CSA
3) FLA (S1-40°C)
4) SK 21xE and SK 23xE devices: For use of safe functions (functional safety: STO and SS1) the restrictions regarding the permissible temperature
range according to BU 0230 must be noted.
5) Fan cooling, temperature-controlled: ON= 55°C, OFF= 50°C,
After-run time when 50°C limit undershot and enable removed: 2 minutes
6) Maximum permissible mains short circuit current
7) "Inverse time trip type“ according to UL 489