8.4.4 Reduced output current due to mains voltage
The devices are designed with thermal characteristics according to the nominal output currents.
Accordingly, for lower mains voltages, higher currents cannot be taken off in order to maintain the
stated power constant. For mains voltages above 400 V there is a reduction of the permissible
continuous output current, which is inversely proportional to the mains voltage, in order to compensate
for the increased switching losses.