8 Additional information
BU 0200 en-3118 251
Pos: 72 4 /Anlei tung en/El ektr onik/FU und Star ter/8 . Zus atzinfor mati one n/Proz essreg ler/ Para meterei nst ellung en Proz essreg ler [SK 1x0E, SK 2xxE, SK 2xxE-FD S] @ 2\mod_1347442621498_388.docx @ 46064 @ 3 @ 1
8.2.2 Process controller parameter settings
(Example: SK 2x0E setpoint frequency: 50 Hz, control limits: +/- 25%)
P105 (maximum frequency) [Hz] :
[ ]
[ ] [ ]




ï£

×
+≥
100%
%P
415
Hzfreq. Setpoint
Hzfreq. Setpoint
Example:
62.5Hz
P400 [-01] (Funct. Analogue input1) : "2" (frequency addition)
P411 (setpoint frequency) [Hz] : Set frequency with 10 V at analogue input 1
Example: 50 Hz
P412 (Process controller setpoint) : CR middle position / Default setting 5V (adjust if necessary)
P413 (P controller) [%] : Factory setting 10% (adjust if necessary)
P414 (I-controller) [%/ms] : recommended 100%/s
P415 (limitation +/-) [%] : Controller limitation (see above)
Note: Parameter P415 is used as a control limit after the PI
controller.
Example: 25% of setpoint
P416 (Ramp time PI setpoint) [s] : Factory setting 2s (if necessary, adjust to match controller
behaviour)
P420 [-01] (Funct. digital input 1) : "1" Enable right
P400 [-02] (Funct. Analogue input 2) : "6" PI process controller actual value