5.5 Control Terminals
BU 0200 GB Subject to technical alterations 107
5.5 Control terminals
Parameter
[factory setting]
Setting value / Description / Note Device Supervisor
Parameter
set
P400 [- 01]
...
[- 07]
Setpoint input function
P
0 ... 17
[-01 = 1 ]
[-02 = 15 ]
[-03 = 0 ]
[-04 = 0 ]
[-05 = 1 ]
[-06 = 0 ]
[-07 = 1 ]
[-01] = Potentiometer 1, function of the potentiometer integrated in the FI (Section. 4.1.3).
The DIP switches 4/5 must be set to “off” (Section 4.1.1) in order for the function to
be influence by this parameter setting.
[-02] = Potentiometer 2, function of the potentiometer integrated in the FI (Section. 4.1.3).
The DIP switches 4/5 must be set to “off” (Section 4.1.1) in order for the function to
be influence by this parameter setting.
[-03] = External analog input 1, current value AIN1 of the I/O extension.
[-04] = External analog input 2, current value AIN2 of the I/O extension.
[-05] = Setpoint module, in preparation
[-06] = Digital input 2, can be set to impulse signal evaluation via the parameter P421=26
or 27. The impulses can then be evaluated as an analog signal in the FI, according
to the function in parameter P400 [-06].
[-07] = Digital input 3, can be set to impulse signal evaluation via the parameter P422=26
or 27. The impulses can then be evaluated as an analog signal in the FI, according
to the function in parameter P400 [-07].
... The setting values follow on the next page.