5.1 Operating display
The abbreviations used are described in Section 8.6 “Abbreviations in this Manual".
Parameter
[factory setting]
Setting value / Description / Note Device Supervisor
Parameter
set
P000 Operating display
0.01 ... 9999 In the SimpleBox (SK CSX-3H) display, the parameter value online selected in P100 is
displayed.
Information about the operating status of the drive can be read out as required.
P001 Selection display
0 ... 63
[ 0 ]
0 = Actual frequency [Hz], is the actual output frequency being supplied by the FI.
1 = Rotation speed [1/min],
is the actual rotation speed as calculated by the FI.
2 = Set frequency [Hz]:
the output frequency equivalent to the actual setpoint. This need not
match the actual output frequency.
3 = Current [A]:
the actual output current measured by the FI.
4 = Torque current [A]:
the torque-developing output current of the FI.
5 = Voltage [Vac]:
the actual alternating voltage being output by the FI.
6 = Link voltage [Vdc]:
the FI-internal DC voltage. Amongst other things, this depends on the
level of the mains voltage.
7 = cos Phi,
the currently calculated value of the power factor.
8 = Apparent power [kVA]:
the actual apparent power calculated by the FI.
9 = Effective power [kW]:
the actual effective power calculated by the FI.
10 = Torque [%]: the actual torque calculated by the FI.
11 = Field [%]:
the actual field in the motor calculated by the FI.
12 = Operating hours:
time that voltage is applied to the FI.
13 = Operating hours enabled:
time that the FI is enabled.
14 = Analog input 1 [%],
current value AIN1 of the I/O extension.
15 = Analog input 2 [%],
current value AIN2 of the I/O extension.
16 =
Position setpoint value Posicon, BU 0210
17 = Position actual value Posicon, BU 0210
19 = Heat sink temperature [°C]: current temperature of the FI heat sink.
20 =
Motor load [%]: average motor load, based on the known motor data (P201...P209).
21 =
Braking resistor load [%]: average braking resistor load, based on the known resistance
data (P556...P557).
22 = Internal temperature [°C]
, current temperature in FI housing.
23 = Motor temperature [°C]
, only in combination with the analog input and appropriate wiring.
52 = Actual position value, incremental Posicon, BU 0210
53 = Actual position value, absolute Posicon, BU 0210
54 = Actual position difference Posicon, BU 0210
55 = Actual position difference Abs./Inc. Posicon, BU 0210
56 = Actual position difference Calculated/Measured Posicon, BU 0210
62 = Stator resistance from identification, value from automatic determination of motor data, P220
63 = Rotor resistance from identification, value from automatic determination of motor data, P220
64 = Stator leakage inductance from identification, value from automatic determination of
motor data, P220
65 = Stator inductance from identification, value from automatic determination of motor data, P220