3.3.6 24V Module, SK CU4-24V-1xx-B
For the internal production of the 24V control voltage for the FI from the available mains voltage (115V/
230V/400V/480V). With this, a separate external 24V control voltage is not necessary.
The analog input for the connection of the potentiometer adapter is therefore also available.
Mains unit for 100-240V, SK CU4-24V-123-B
Mains unit for 380-500V, SK CU4-24V-140-B
1x analog input (e.g. Potentiometer Adapter)
1x impulse output
Green LED = 24V
Module
SK CU4-24V-...
Function
Pin
Labelling
1
44
+24V, supply voltage 24V
Supply voltage for an SK 200E or other module, 24V
±15%, max. 400mA
The module can also be supplied with 24V (in this case
without L1/L2), in order to only use the voltage/frequency
converter (analog function)
2
40
GND, reference potential
3
44
+24V, supply voltage 24V
4
40
GND, reference potential
5
11
+10V, reference potential
Potentiometer supply voltage,
max. load 5 mA
For connection
of a 5-10kOhm
potentiometer
6
14
AIN1+, analog input
Analog input, 0-10V, 8bit resolution
A 500 burden resistor for evaluation
of 0/4-20mA is enclosed.
7
12
0V, analog Ground
Reference potential for analog
signals.
8
B1
FOUT, frequency output
Impulses, for evaluation via the digital input function P420
[02]/[03] = 26/27 and the analog meaning in P400
[-06]/[-07].
9
40
GND, reference potential Reference potential
Electrical isolation
10
Mains connection, according to module
110-240V or 380-500V
11
L1
L1, mains connection 1
st
phase
12
13
L2
L2, mains connection, 2
nd
phase
14
15
PE
PE, Earth
As required, does not need to be connected.
16
PE
PE, Earth