EasyManua.ls Logo

nord NORDAC SK 200E - Profibus Module, SK CU4-PBR

nord NORDAC SK 200E
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.3 Internal Customer Unit
BU 0200 GB Subject to technical alterations 63
3.3.2 Profibus Module, SK CU4-PBR
Bus module for the control, parameterisation and diagnosis of up to four frequency inverters via ProfiBus.
Baud rate: Max. 12 MBaud, automatic detection
Protocol: DPV 0 and DPV 1
2x digital inputs
Address via DIP switches
Termination resistor via DIP switches
Automatic PPO detection
Status LED: BG status, BG fault, DIN1, DIN2,
Bus status, Bus fault
Details in Bus Manual BU 0250 (www.nord.com)
Module
SK CU4-PBR
Function
Pin
Labelling
1
44
+24V, external 24V supply
External supply voltage of module
24V ±20%, 150mA
2
40
GND, reference potential
3
C1
BDIN1 / digital input 1
Digital inputs, SPS-compatible as per EN61131-2,
low: 0-5V, high: 11-30V
…, used for further processing via the bus.
4
C2
BDIN2 / digital input 2
5
77
SYS+, system bus
System bus connection to FI
6
78
SYS-, system bus
7
40
GND, reference potential
Parallel to Pin 1/2
8
44
+24V, external 24V supply
Electrical isolation
9
82
PBR B, Profibus, red
Profibus data cable for external communication,
incoming
10
81
PBR A, Profibus, green
11
46
GNDB, Bus Ground Bus reference potential
12
83
RTS, “Ready to send” RTS
13
47
+5VB, Profibus 5V Bus 5V
14
82
PBR B, Profibus, red
Profibus data cable for external communication,
outgoing
15
81
PBR A, Profibus, green
16
46
GNDB, Bus Ground Bus reference potential

Table of Contents

Related product manuals