2 Mounting and Installation
BU 0200 GB Subject to technical alterations 33
2.6.2 Motor cable (X2 - U, V, W, earth)
The motor cable may have a total length of up to 100m if this is a standard cable. If a screened motor cable
is used, or if the cable is laid in a well earthed metal conduit, the total length should not exceed 20m.
Note
: Please also note Section 8.2 EMC limit
classes.
Note
: For multiple motor use the total cable length
consists of the sum of the individual cable
lengths.
Cable cross-section:
0.5 ... 6mm
2
rigid/flexible cable
0.2 ...
AWG 20-10
Tightening torque
1.2 ... 1.5Nm
2.6.3 Brake resistor connection (X2 - +B, -B)
Terminals +B/ -B are intended for the connection of a suitable braking resistor. The connection should be as
short as possible.
Note
: The large amount of heat produced by the
brake resistor must be taken into account.
Cable cross-section:
0.5 ... 6mm
2
rigid/flexible cable AWG 20-10
Tightening torque
1.2 ... 1.5Nm
PE
Motor