Operating Parameters
B-6
Part 1073401_07
E 2021 Nordson Corporation
Standard (contd)
13
Change Hose 2 Output to Electric Applicator
Activation
Description:
Changes the proportioned 240 VAC current that is provided to the hose 1
heater to a switched 240 VAC current that is used to activate a
manifold-mounted electric applicator.
Value:
0 (disabled)
1 (enabled)
Resolution:
—
Default Value:
0 (disabled)
Format:
—
Use:
Use only when a Nordson manifold-mounted electric applicator is
installed and a switching device is connected to the melter’s switch
receptacle. Refer to the electric applicator manual for information on
mounting and using the applicator.
14
External Communications Lock-out
Description:
Used as a safety feature when performing maintenance on the melter.
Prevents external control of the melter through standard or optional
inputs/outputs or network communications (optional)
Value:
0 (disabled)
or
1 (enabled)
Resolution:
—
Default Value:
0 (disabled
Format:
—
Use:
Set parameter to 1 (enabled) before performing any maintenance on the
melter. When enabled, all external control of the melter stops until the
parameter is once again set to 0 (disabled).